could not change label - all labels used

Issue
Saving a custom template, gives 'could not change label' or 'all labels used' message.

          

Product Line
ION meter

Environment
Designer

Cause
Pasting a large custom framework in a meter in which the output register labels have been modified from the default for a large number of modules.

Resolution
There is a limit to the number of modules whose output register label can be customized from the default.  The only workaround is to modify the output register label to a default one in a module that does not necessarily need to have a custom label.  This will provide an unused label which can be used in any other module's output register.
 