FAQ : How to transfer WebVisu by FTP to M241 M251 M258 without stopping in exception

  • The first step is to generate files to be transferred on the controller.
When offline, select "Build -> Generate code" in menu.

Controller program generation gives 3 files :, Application.crc and
A folder called "visu" is created : it contains WebVisu components.
  • FTP client has to be configured to transfer these files in "Binary" mode : see FileZilla screenshot in attachment.
  • Now simply transfer files to /usr/App and all of the files in visu folder to /usr/visu.

Controller application is now ready to run and WebVisu will be available as soon as the controller will run.