While Importing xml file in the BMXNOR0200 firmware version V1.6 there is error saying import not successful ?

The XML file contains the module and protcol configuration parameters. One can easily export these parameters into a XML file.
This file can later be restored into the module by importing it from the module webpage.
However if the module commnication  channel parameters are not defined, then you get an error import not successful while importing the xml file.




So its very important to define the communicatoin channel parameter before exporting the configuration into the xml file.


 