Download the Vijeo Designer project as a filesystem to a USB stick. It downloaded to the first Magelis fine but not the second one, why?

Issue:
Download the Vijeo Designer project as a filesystem to a USB stick.  It downloaded to the first Magelis but not the second one, why?

Product Line:
Magelis XBTG/GH/GK/GT, HMIGTO/STO/STU, Vijeo Designer

Environment:


Cause:


Resolution:
The reason is that by default in Vijeo Designer, the Install Option is set for "Single Install".  Which only allows to load the project one time to a Magelis target.  The file on the USB stick will then get overwritten and can not be used for the second time.  Your option would be to set the Install Option to "Multi Install" or rename the file on the USB stick from AGPBAK.SYS to AGP.sys.