Technical FAQs

Ask a Question

How to add Web Image Gadget for PME 7.2.2

When running the SQL query to add Web Image Gadget to PME 7.2.2 obtained from the Technical Publication link below:
The SQL query fails with the below error

Product Line
Power Monitoring Expert 7.2.2
Power Monitoring Expert 7.2.2 for Data Center
Power Monitoring Expert 7.2.2 for Health Care

Web Applications "Dashboards"

The SQL script from the above technical note link, checks to see if the Application Modules database is at database schema version 3. In PME 7.2.2 the database schema was changed and upgraded to version 4. 

An updated version of the webgadget SQL query is attached.

NOTE: This SQL query has been modified to work with any version of PME 7.2.2.
NOTE: This issue has been resolved in PME 8.0 as the Web Image Gadget is installed as part of PME 8.0 installer.