Technical FAQs

Ask a Question

Why do I see 115 VAC on the outputs of the BMXDAO1605 when there is no load connected to to module?

This is normal when attempting to measure a triac output with no load.  Triac outputs cannot be accurately tested without a load.
The high impedance of the voltmeter will introduce enough of a load to cause the applied voltage on the triac to be seen. 
Test with a load applied to the triac and you'll get a more meaningful measurement.

Product Line: Quantum, M340,

Environment: n/a

Cause: n/a

Resolution: n/a

Was this helpful?
What can we do to improve the information ?