Technical FAQs

Ask a Question

What can cause an OLF or overload fault on the ATV61 and ATV71 drives?

Issue:
What can cause an OLF or overload fault on the ATV61 and ATV71 drives?

Product Line:
Alitivar ATV61 and ATV71 drives.

Environment:
All

Cause:
Motor is pulling to many amps and drive is tripping out on OLF fault.

Resolution:
OLF= Overload fault this fault is triggered by excessive motor current.
Check your Motor thermal setting in the Simply Start menu make sure it equals what your Motor FLA ratings.
Check your load.  Run the motor and using the monitoring menu 1.2 check to see what the LCR motor parameter is displaying.  If the motor is pulling to many amps you will need to check to see what is causing your motor to overload.

Was this helpful?
What can we do to improve the information ?