Technical FAQs

Ask a Question

How to add a custom image/logo to reports in ION Enterprise or Power Monitoring Expert?

Issue
A user may want to add a custom image or logo in place of the default "Schneider Electric" logo that is displayed on reports.



Product Line
ION Enterprise 6.0
SPM 7.0.1
Power Monitoring Expert 7.2.x
Power Monitoring Expert 8.x

Environment
Web Applications "Reports"

Cause
It may be desired to replace the default logo displayed on reports

Resolution

For ION Enterprise 6.0 and SPM 7.0.1: 
- Navigate to http://localhost/Reports$ION or http://localhost/Reports or http://localhost/ReportsION or http://localhost/Reports_ION
  (This is dependent on how the system is set up) 
- Next, navigate through ION Reports --> ION Reports Packs --> Default Reports 
- Click on Report-Logo.jpg. The "Report-Logo.jpg" file needs to be replaced with a custom logo file with the same name. (Review screen shot below) 
- Note: The image file is required to be no larger than 250x100.
- Click on 'Upload File' 
- Browse to the custom logo file and make sure the name is "Report-Logo.jpg"
- Now, every report that is run from the Default Report Pack will have the new custom logo at the top of the report.




For PME, navigate to the Power Monitoring Expert install directory

For PME 8.0 and PME 7.2.x:
Navigate through following directory: 
...\Schneider Electric\Power Monitoring Expert\web\ReportDepot\ION Reports\ION Report Packs\Default Reports

There will be a JPEG file in the folder named "Report-Logo". The image file is required to be no larger than 250x100.

If you replace the image with a different image that is named "Report-Logo" the new image will be displayed on reports (as shown in screen shot below).

For PME 8.1 or later:
​...\Schneider Electric\Power Monitoring Expert\config\reports

There will be a JPEG file in the folder named "Report-Logo". The image file is required to be no larger than 250x100.

If you replace the image with a different image that is named "Report-Logo" the new image will be displayed on reports (as shown in screen shot below).

Was this helpful?
What can we do to improve the information ?