How to clear and install I/O units and Arc sensors for the VAMP321 arc flash mitigation relay

Issue: Need to clear and install I/O units and Arc sensors.

Resolution:
Press the Down arrow until Arc is selected. Press the OK button then scroll down until you see Clear at this point press the "i" button > press OK > this will request a password the default password for edits is 2 > once this is entered press OK. This will take you back to the Clear selection > Press OK > Select Clear and press OK. This will reset all of the Arc Sensors and I/O units for the VAMP 321. 


To install I/O units and Arc Sensors scroll up to Install > Press OK > Select Install > Press OK. This will reinstall all of the I/O units and Arc Sensors that are connected to the unit.