TSXSCP114 and TSXSCP1114 serial communications baud rate ranges

 

Goals and Symptoms

This Resolution clarifies the baud rate ranges for the TSXSCP114 and TSXSCP1114 RS422/RS485 Serial Communication cards.

 
Facts and Changes

Unity allows the user to select the same baud rate ranges between the TSXSCP114 and TSXSCP1114 even though their baud rate ranges are different.  Unity does not limit the selection of the baud rates based on the communication card configured.
 

Causes and Fixes

 The baud rate ranges are as follows:

    TSXSCP114 - 1200, 2400, 4800, 9600, 19200

    TSXSCP1114 - 1200, 2400, 4800, 9600, 19200, 38400, 57600

The default baud rate is 9600.

Additional Information

Reference Premium and Atrium using Unity Pro Asynchronous Serial Link User Manual, 10/2013.  Part number, 35006178.12.