Why is my M1E not IO scanning my Advantys STBNIP2212 island?

Title

 

Issue

 

Product Line

 

Environment

 

Cause

 

Resolution

Ensure that the ethernet network, IP addresses and subnet masks are configured properly and all devices can be pinged.  Now verify that in the M1E IO scanner setup that the 'Read Ref Slave' memory location is set for 45392 and not 40001 as would be the case if scanning a Momentum IO base with an ENT communication adapter.  This is a common error with Advantys STB.