How may the Zone Selective Interlocking (ZSI) contacts be modified on a Sepam 80 series relay?

Issue: Need to modify the ZSI contacts

Product Line: Sepam 80 series relay

Resolution: The ZSI contacts are configured in the Control Matrix within SFT2841. To modify the contacts associated with ZSI navigate to the Control Matrix then click on Logic > Outputs. This will allow you to change the contacts associated with any of the Sepam Relays predefined logic.