What are the default Modbus serial port settings for the COM'X 200?

Issue:
What are the default Modbus serial port settings for the COM'X200?

Product Line:
COM'X200
EBX200

Environment:
COM'X200 serial communications

Cause:
The default Modbus serial port settings of the COM'X200 may be unknown.

Resolution:
Baud Rate: Default - 19200
Options available are  1200, 4800, 9600, 19200, 38400, 57600, and 115200


Parity: Default - Even
Options available are Odd, Even and None


Number of stop bits: Default - 1
Options available are 1 or 2


Timeout: Default - 1000ms  
Options between 100-10000ms


Terminator Resistance: Has a value of 120 Ohms and should be activated when the COM'X200 is at the end of a Modbus daisy chain.