How can all 8 channels of a BMXART0814 module be used to read thermocouples without the ABE7CPA412 block for cold junction compensation?

Title

Can the BMXART0814 module be used without the ABE7CPA412 and maintain use of all 8 channels for Thermocouple operation?

Issue

 

Product Line

Modicon M40

Environment

 

Cause

 

Resolution

Yes, using a 2-wire PT100 RTD wired to channel 4 on terminals EX+ and EX-.  This will allow all 8 channels of the BMXART0814 to be used for thermocouple operation as configured and with one CJC termperature.