There is a download security set on the HMI XBTGT6330. But I do not remember the password and is locked out of the Magelis. How can I recover or download an application to the target?

Issue:
There is a download security set on the HMI XBTGT target.  But I do not remember the password and is locked out of the Magelis.  How can I recover or download an application to the target?

Product Line:
Magelis XBTGK/GT/GC/GH, HMIGTO/GTU/STO/STU, iPC, Box PC, Panel PC

Environment:


Cause:


Resolution:
There is no way to recover the password from the Magelis.  Your options are to modify the security settings and download as a filesystem to a CF.  Then force the Magelis to download the application from the CF card.  Or use the Runtime Installer program and run the runtime recovery on the target.