Technical FAQs

Ask a Question

What causes Unity error "Due to alignment constraint, you have to decrease or increase topological address index of 1"?

In Unity Pro, 32 bit datatypes must be mapped to an even address boundary when using the M340 PLC.
For example,   variables  of REAL  or DINT datatypes must be mapped to %MW2, not %MW1.
Was this helpful?
What can we do to improve the information ?