Summary Report Pack will not install via the Web Interface

Summary Report Pack will not install via the Web Interface

Product Line
Summary Reports Pack

StruxureWare Power Monitoring 7.0.x and StruxureWare Power Monitoring Expert 7.2 with Summary Reports Pack

Cannot install Summary Report Pack via the SPM/PME Web interface

Use the ReportPackUtil.exe found in the \system\bin folder of the SPM/PME installation.

The command to install the report pack would be:

ReportPackUtil.exe –root <SPM/PME\web> - install <ReportPackName>

<SPME/PME\web>: is the directory where SPM/PME is installed in the server

<ReportPackName>: this is the name of the report pack without the file extension name


ReportPackUtil.exe -root "C:\Program Files (x86)\Schneider Electric\Power Monitoring Expert\web" -install "Summary Report Pack 4.2"

If the report pack does not install through command line a stack trace will be produced with details regarding why the install did not succeed.  One of the most common reasons is the stack trace shown in the screen shot below.

The error states "The process cannot access the file 'C:\Program Files (x86)\Schneider Electric\ION Enterprise\system\bin\Reporting.LogicalMeasurementExtension.Argument.dll' because it is being used by another process.
This can be caused by the ION Report Subscription Service running.
This error can occur when attempting to install any Report Pack from command line so the service needs to be stopped before it can be installed successfully.

In order to stop the service go to the start menu and search for "services.msc" to load the services interface.
On the service "ION Report Subscription Service" right click and select the Stop option.
Run the Report Pack installer from command line once again and, once it succeeds, then right click on the ION Report Subscription Service and select the Start option.