Using Unity Pro how can I copy all %IW topological data words to a memory word array (%MW100:16)?

The %IW topological addresses can not be used in arrays. For this reason, you can not use %MW100:16 := %IW0.2.0:16. What you will need to do is individually move these words one at a time. %MW100 : = %IW0.2.0, %MW101 : = %IW0.2.1...  etc.