Technical FAQs

Ask a Question

What are the processes associated with PowerLogic Scada?

In cases that a project does not start or shut down properly, it is advised to check the processes.  In the case the project did not shut down properly, the process can be killed manually using Windows Task Manager.  This way upon a restart of Runtime Manager, the project starts without any problem.

The example below shows a project with six I/O Servers (numbered 2, 4, 6, 8, 10 and 12), a Trend Server, one Alarm Server and a Client (represents the main project); a total of 9 processes as shown in Runtime Manager.


The processes above can be verified in Windows Task Manager as shown below.  There is an entry for each of the above 9 processes, each labeled Citect32.exe *32.  Note the one-to-one correspondence among the Process IDs in Task Manager and Process IDs in Runtime Manager.  For example PID 22716 in Task Manager corresponds to IOServer6 as show in the above picture.


In case PowerLogic Scada application is open for editing a project, there will be three additional processes.  Process names and their corresponding application are shown below:

CtDraw32.exe *32     Citect Graphics Builder
CtEdit32.exe *32        Citect Project Editor
CtExplor.exe *32        Citect Explorer

Was this helpful?
What can we do to improve the information ?