How long does it take 3710 ACM and 3720 ACM meters to initialize the relay outputs?

From the source code of the firmware for 37xx meters, the meter will suppress relays, setpoints, and alarms for 3 seconds during power up. In other words, relay outputs will be inhibited until the 3 second initialization period is over after a power up. There is no way to change these values since it is coded into the firmware.