Which firmware version supports functionality of the PM8 Ethernet Communication Card (PM8ECC) with the Series 800 Power Meter (PM8)?

Issue
Which firmware version supports functionality of the PM8 Ethernet Communication Card (PM8ECC) with the Series 800 Power Meter (PM8)?
 
Product
PM800 Series Power Meter, PM8ECC
 
Environment
Mounting PM8ECC on PM800 Series Meter
 
Cause
The PM800 series meters had been out several years before the PM8ECC became available, so the firmware may not be the latest. As a result, PM8ECC will not function correctly.
 
Resolution
The Series 800 Power Meter (PM8) MUST have 10.6 firmware or later in order to support the functionality of the PM8 Ethernet Communication Card (PM8ECC).

To verify the firmware version from the front panel of the meter, follow the steps below.
1. Press MAINT > DIAG > METER.
2. Verify that the number before OS, RESET, and DL is 10.600 or higher.
3. If the meter firmware is not up-to-date, then meter firmware must be updated.  One or all three firmwares may need upgrading (OS,RS, or DL).

NOTE: In order to upgrade the firmware, you will need the Download Firmware Upgrade Utility (DLF3000), which is provided on the
PM8ECC Technical Library CD-ROM or can be downloaded from  Firmware Upgrade - Instructions and Downloads.  
If you need assistance using DLF3000, refer to the Help file.