Can the ribbon cable for the Branch Circuit Monitor (BCM) be extended with a male-to-male connector and a second ribbon cable?

The ribbon cable can be extended up to 20 feet maximum. Two cables cab be connected together using a male-to-male pin connector. It is best to use a solid ribbon cable when possible and keep the cable as short as possible. Any extra connections used can create noise and distortion which can decrease accuracy.



  • Date Created: September 13, 2007
    Last Revised: February 15, 2008
    Public
    Original Author: MN
    All content © 1992-2008 Schneider Electric

Legacy KB System (APS) Data: RESL191105 V1.0, Originally authored by PhHa on 02/15/2008, Last Edited by PhHa on 02/15/2008
Related ranges: BCM (Branch Circuit Monitor)