Error 16 in Advanced Reports when creating or editing a report. You do not have the right to “Add objects to the folder” or "Edit objects".

Goals and Symptoms

SMS user levels 2 5 go through creating the report and when pressing Finish at the final step get an Error 16 with message that they dont have the rights to Add objects to the folder.
Summary

The default SMSPE 4.0 Operator account has an security level of 5. So the user is part of the SMS AR Operators group in CE (SMSPE levels 2-5 map to this group). This group has view on demand rights (see rights on PowerLogic Reports folder). However this group does not have rights to add objects to that folder. Therefore, when the user attempts to create/edit a report they will get an error when clicking Finish on the final step of the wizard. The resolution is to change the Access Level in Advanced Reports, Crystal Management Console for the "SMS AR Operators" to allow the user to Edit and Create objects to folders.

Causes and Fixes

Symptoms

Error publishing new report (report name), you do not have the right to 'Add objects to the folder' (id -1) fc "table' (id -215). Please contact your system or permissions administrator if you require this right.

Error publishing new report (report name), you do not have the right to 'Edit objects' (id -6) for 'report name' (50526). Please contact your system or permissions administrator if you require this right.


Cause
The cause is that System Manager Software (SMSPE) 4.0 users, with security Level 2 - 5, do not have permissions to the folders.

Resolution

Change the rights on the PowerLogic Reports Folder for the SMSPR AR Operators group to allow objects to be added and modified.

1. Log in to Crystal Management Console as the Administrator account

2. Click on Folders

3. Click on PowerLogic Reports

4. Click on the rights tab. You should be on the screen below.

5. Change the access level drop down from SMS AR Operators from View On Demand to Advanced...

6. This will switch to the Advanced rights (Or Click on the Advanced link next to the drop down. Only change the following (level defaults for other items).

Explicitly Granted "Add Objects to Folder"

Explicitly Granted "Edit Objects"

Click Apply.

It may be necessary to deny the following rights but they are not required to resolve the issue:

Explicitly Deny "Modify the rights users have to objects" 

Explicitly Deny "Delete Objects"

Explicit Deny "Delete Instances"

 

Attachments

(Removed Image URL: /PubResEXPORT.nsf/2b87ee90be777fc085257c28006ee4ef/999e471a5aee7216c12573d900160eab/fl_block_5/0.1A60?OpenElement&FieldElemFormat=gif)

  • Original article#
    Date Created: September 24, 2007
    Last Revised: January 22, 2008
    Public
    Original Author:KT
    All content © 1992-2008 Schneider Electric

Legacy KB System (APS) Data: RESL190751 V1.0, Originally authored by PhHa on 01/23/2008, Last Edited by PhHa on 01/23/2008
Related ranges: SMS Add-on
Was this helpful?
What can we do to improve the information ?