During installation of System Manager Software (SMS) Software, the following error message appears immediately after clicking on the autorun or setup.exe. "String Path_LONGSRCDIR was not found in string table"

 

The directory path to the setup.exe file contains spaces. Remove spaces from directories and the install will proceed. This can occur when someone installs SMS from location (PC or network) other than the standard software distribution CD.