Technical FAQs

Ask a Question

171CCC9x0x0 M1E Processor IEC Exec. Upgrade to v.1.29

Release Notice

The purpose of this resolution is to inform Momentum M1E users that the IEC Exec. has been upgraded (Feb. 2008) to version 1.29.

Goals and Symptoms

IEC Exec version 1.29 resolves the following issues:

  • 1) Under certain conditions, the M1E would not respond to a second ARP.

    2) If two or more MSTR TCP function blocks (ie. Read_Reg) are programmed and active at the same time, periodically one of the blocks could freeze operation for 3-5 minutes, then recover on its own.

    3) PSH flag is no longer set in the SYN and FIN packets. This caused communication problems between the M1E and a third party device.

    4) Fixes an issue in the M1E web page where the 'TCP Retry' counter would increment every time a TCP MSTR block was activated.

Causes and Fixes

Installing IEC Exec. v.1.29 resolves the above mentioned issues.

Was this helpful?
What can we do to improve the information ?