How long does it take the digital input for logic discrimination (ZSI) to be recognized by the Sepam relay and setting group A to be blocked?

It takes about 13 ms (one cycle time of the control reading) operating time for the relay to recognize and react to an input change.
Note: For a Sepam series 20, only input I13 can be used to receive a blocking reception.


  • Date Created: February 22, 2008