What is the maximum number of Active Connections allowed on an EGX100 Gateway and can it be changed?

Issue
What is the maximum number of Active Connections allowed on an EGX100 Gateway and can it be changed?

Product Line
EGX100

Environment
Active Connections

Cause
Information is needed on how many simulataneous connection an EGX100 can allow.

Resolution
The default number of Active connections allowed on an EGX100 Gateway is 32 Modbus/TCP Server Connections. This value can be changed to up to 48 connections with Firmware 2.7 up to 2.9 inclusive.
This can be done by connecting to the Gateway's web page and then adding /AdvCommsSetup.htm to the address of the gateway. This will bring you to the Advanced setup page for communications.