How to enable the Configuration Report in ION Setup for the ION7550RTU Meter.

The reports section in ION Setup is not enabled by default for the ION7550RTU and therefore the meter configuration report is also not enabled.

Product Line:
ION7550RTU Meter

ION Setup 3.0

This feature is disabled by default.

In order to unhide the feature, open the QuickIon.cfg file for the ION7550RTU from the …\Schneider Electric\ION Setup\Tables\PML7550RTU directory with Notepad or any text editor software.
Change line 8
From: AssistantCount=9
To: AssistantCount=11

Displays(Assistant10) and Reports (Assistant11) do exist in the code, but they are hidden. Therefore, to unhide the feature, change the 9 to 11 in the AssistantCount line.