Technical FAQs

Ask a Question

GetNativeSQL - How to use Vista to create SQL Queries

Issue
A user would like to create a SQL query to obtain data directly from the ION_Data database. SQL Server Management Studio requires users to have advanced knowledge in writing SQL queries where as the Vista application provides a convenient wizard interface to create the query. The Data Log Viewer provides an "Edit SQL" option to view the Vista query, but these commands do no work in SQL. 

Product Line
ION Enterprise 
StruxureWare Power Monitoring 7.0.x
Power Monitoring Expert 7.2.x
Power Monitoring Expert 8.x

Environment
Vista
SQL Server Management Studio

Cause
The queries created by the Vista Wizard can not be directly run in SQL. 

Resolution 
*Warning: Irreparable database damage can occur. This procedure should only be performed by users familiar with SQL Server Management Studio. Databases should be backed up prior to performing this procedure.* 

There is a command called 'GetNativeSQL' can be added to the "Edit SQL" in the Vista Wizard that will allow the user to obtain the native SQL commands required to query the ION_Data database directly in SQL Server Management Studio. 

See attached document for instructions. 

Was this helpful?
What can we do to improve the information ?