Technical FAQs

Ask a Question

Installing new M340 CPU SD memory card.

1. Make sure new SD card is in the Unlock position.
2. Insert new SD card into M340 memory card slot and the LED will turn ON.
3. Open the Animation Table Window.
4. Add system bit %S65.
5. Turn on the Modification button.
6. Enter value 0 for %S65 and close door.
7. Start PLC.

Related ranges: Modicon M340
Was this helpful?
What can we do to improve the information ?