How do I know what the default IP address is for a Twido controller?

The default IP address is 85.16.x.y, where x.y is derived from the last two octets of the MAC address converted to decimal.
If the MAC address is 00.80.F4.81.45.22, the last two octets is 45.22. These must be converted to decimal. 45hex = 69dec and 22hex = 34dec.
Therefore, the default IP address would be