What is needed to replace a Model 85 Temperature Controller with a Model 98A Retrofit Kit ?

Issue:
Retrofit
Product Line:
Medium Voltage Dry Type Transformers
Environment:
Temperature Controllers
Cause:
Upgrade
Resolution:
Use a kit part # 24806-001-50 for Indoor Xfmer or  24806-001-51 for Outdoor Xfmer. Kit comes with K thermocouples to replace existing thermistors . Include serial # of transformer so the controller can be set for correct temperature rise otherwise 80C is default .
 
Attached is the document "Instructions for Field Retrofit of a Model 98A Digital Temperature Controller in place of a Model 85 Temperature Controller" 24806-003-01 Rev 0
This document contains a set of instructions for retrofitting a Model 98A Digital Temperature controller in place of an existing Model 85 Temperature controller.

Model 98A Retrofit Instruction Bulletin.pdfModel 98A Retrofit Instruction Bulletin.pdf

Legacy KB System (APS) Data: RESL212429 V1.0, Originally authored by DaFr on 09/03/2013, Last Edited by DaFr on 09/03/2013
Related ranges: Model 98 DTC