Technical FAQs

Ask a Question

PM1000, PM1200, and EM6400 block registers

Certain registers must be read as a "block" from the PM1000, PM1200, and EM6400 meters. In order to read these registers, one must set the starting register to 3001, then 20 registers must be read in a single read. Attempting to read these registers in any other manner will result in either a time out or an error.The example in the picture below shows an scenario.

Note: "Function Code: O3H Read" is stating that these registers are Holding Registers.
The PowerLogic PM1000 Series Power Meters User Manual can be found here. It includes the PM1000/PM1200/EM6400 register list.


Legacy KB System (APS) Data: RESL211609 V1.0, Originally authored by DaFr on 05/30/2013, Last Edited by DaFr on 05/30/2013
Related ranges: PM1000 series, EM 6400 DigitAN