What is the maximum allowable main board temperature you can see in the diagnostic module of an ION8600?

There is a main board temperature in the diagnostic module of ION meters; for the ION8600, the maximum allowable temperature is 85C. Anything above that will reduce the operation of the meter. The range of values which can be seen are from -55C to 125C. A value of 127 is displayed during a fault condition.


Legacy KB System (APS) Data: RESL211346 V1.0, Originally authored by MaTh on 05/02/2013, Last Edited by MaTh on 05/02/2013
Related ranges: ION8600