Are PowerLogic devices without onboard logging configured by default to automatically log in an ION Enterprise or Power Monitoring Expert system?

Issue
User wants to know if data coming from PowerLogic meters are being logged automatically in ION Enterprise or Po
wer Monitoring Expert (PME) system.


Product Line
PowerLogic meters

Environment
ION Enterprise
Power Monitoring Expert (PME)
Modbus Device Importer

Resolution:
*Warning: Take backups of any files prior to modifying them. Ensure the backups are in a location that will not be overwritten (i.e. the Desktop). 

While the devices may be built into the system and there are device drivers to support them, the logging is not enabled by default for all parameters.

To modify/configure the logging, access Modbus Device Importer (MDI) from Management Console.
Once Management Console is open click Tools > System > Modbus device importer
Click File > Open > Choose the device driver from the list > Open

Note: You may see error message statement "This device type cannot be opened by this application." when trying to open a device type in Modbus Device Importer.
If you see that message, that means that device driver is not editable using MDI and may get corrupted if you try to modify it.
please click OK and stop trying to change configuration for that device driver.


Click Configure Logging and Calculation and check the values that you want to log by placing a checkmark in the 'Log' column.

Once finished choosing your options Click File > Save > Close the MDI and ION will now be logging the selected values.