CM2000 (CM2) datalogs are being reset/disabled when using ION setup

When using ION setup to configure the datalogs for a CM2000 series power meter, it may not send the changes made to the meter. It will instead reset or disable the datalog, or set the number of channels to zero. This is due to the memory in the CM2000 being maxed out. Lower the number of records and/or channels to resolve this issue.