How are kW and kWh resets performed on a Multi-Circuit Meter (MCM)?

In order to perform resets, there must be communications established to the MCM.
Resetting kWh
In order to reset kWh on a MCM, write a value of 0 to either of the kWh integer registers (registers 1 or 2).

Resetting Min/Max/Avg kW
Writing ANY value to any of the minimum kW, maximum kW, or average kW integer registers (registers 28, 29, and 27, respectively) rests all three of these values.