Technical FAQs

Ask a Question

What is the difference between an EGX100 and a TSXETG100?

Product Line
EGX100

Environment
Part number

Resolution
The EGX100 is a Square D branded Ethernet gateway and the TSXETG100 is a Telemecanique branded Ethernet gateway. The units are physically the same, but offer different transmission modes for serial communications.
The EGX100 supports Modbus RTU, Jbus, PowerLogic (SY/MAX), and Modbus ASCII.
The TSXETG100 only supports Modbus RTU and Modbus ASCII. PowerLogic legacy devices such as CM100/200s and CM2000s, as well as SEPAM Relays, would be unable to communicate through a TSXETG100.

Was this helpful?
What can we do to improve the information ?