Reporter on an ION Enterprise client installation will not query the ION_Data database. Reporter gives the error "SQL Server does not exist or access denied" or "Specified SQL server not found".

Goals and Symptoms

Reporter gives one of the following errors:
*ERROR* Error -2147467259 [[DBNETLIB]]ConnectionOpen (SQL Server does not exist or access denied.) has occured in Microsoft OLE DB Provider for SQL Server

*ERROR* Error -2147467259 [[DBNETLIB]]ConnectionOpen (Connect()).[Specified SQL server not found.) has occured in Microsoft OLE DB Provider for SQL Server

Management Console, Vista and Designer work after adding the port to the database connections in the registry, however previously created reports will not run. The database connections are now <ServerName>\ION,1433 instead of <ServerName>\ION. Creating a new report works. Adding ,1433 to the database connection in Reporter does not work. Connecting to the database and querying with excel allows a valid connection if ,1433 is added to the SQL instance name. The same report works on the server and could possibly work on other client machines.

Causes and Fixes

Do the following to resolve this issue:
1) On the ION Enterprise server machine go to the report folder ...\ION Enterprise\config\reports
2) Open the report that won't run on the client.
3) Go to format > sheet > unhide and choose |PRIVATE|Datasheets
4) Change column Y from <ServerName>\ION to <ServerName>\ION,1433
5) Go to format > sheet > hide and then save the excel sheet.

The report should now work on the client computer.

Date Created: January 19, 2009
Last Revised: April 29, 2009
Public
Original Author: MN
All content © 1992-2009 Schneider Electric


Legacy KB System (APS) Data: RESL198399 V1.0, Originally authored by MiNe on 04/30/2009, Last Edited by MiNe on 04/30/2009
Related ranges: ION Enterprise V5.5, ION Enterprise V5.6