Technical FAQs

Ask a Question

ION Enterprise Webreach shows HTTP Error 401.3 and says "Unauthorized: Access is denied due to an ACL set on the requested resource."

Verify that either the group users, or the user NT AUTHORITY\NETWORK SERVICE has at least if not more permissions than what is shown below in the screen shot.
1) Navigate to the ION Enterprise folder
2) Right click on ION Enterprise and go to properties
3) Go to the security tab
4) Add either the users group or the NT AUTHORITY\NETWORK SERVICE user to the list of users and groups with access to the folder.
5) Verify that the permissions are set to a minimum of what is shown below:



Date Created: February 25, 2009
Last Revised: April 29, 2009
Public
Original Author: MN
All content © 1992-2009 Schneider Electric


Legacy KB System (APS) Data: RESL198395 V1.0, Originally authored by MiNe on 04/30/2009, Last Edited by MiNe on 04/30/2009
Related ranges: ION Enterprise V5.6
Was this helpful?
What can we do to improve the information ?