Is it possible to configure a Form 9S 8600/8650 meter as a Form 35S?

Customer purchased a ION 8600/8650 with "Form Factor" of 9/29/36S Base and wants to wire as a Form 35s

Product Line

Installation and wiring

Customer purchased 9s meter for use in form 35s environment

It is possible to configure a form 9S ION 8600/8650 meter as a form 35S, but a form 35S cannot be converted into a 9S since the form 35S doesnt have a blade for I2 connection. Following the diagrams below, the meters connection terminals must be rewired to match. The firmware is the same for all types of form factors hence, it is not required to change the firmware.