Reporter generates Automation Error in pmlRepGen

Goals and Symptoms

Reporter shows automation error in PML Repgen

Error reads:

  • Error -2147221080 (Automation error) has occured in pmlRepGen

Causes and Fixes

This can be caused by incorrect database rights:

  1. Open SQL Management Console and expand the tree down to ION_Data > Users.
  2. In the right hand pane double click on Report to show properties.

  3. It should only have Public, db_datareader and ION_Reader checked.
  4. If you need to alter this cancel out of the above screens and expand the tree in the left hand pane and go to Security > Logins.
  5. Double click Reports in the right hand pane > Database Access tab> now edit the database role (to allow the three access rights mentioned in step #3).





Last Revised: November 13, 2007
Applies To: ION Enterprise
Public
All content © 1992-2007 Schneider Electric

Legacy KB System (APS) Data: RESL189154 V1.0, Originally authored by KBAdPM on 11/14/2007, Last Edited by KBAdPM on 11/14/2007
Related ranges: ION Enterprise V5.6, ION Enterprise V5.5, ION Enterprise V5.0