Can the energy on a ION6200 be reset from the front panel?

User wants to reset the energy value on an ION6200 from the front panel

Product Line

Front display of ION6200

A possible cause could be that the meter is moved to a new location, and the accumulated values need to be reset.

For non-revenue sealed meters, firmware version v205 and later allows the energy (kWh) register to be reset from the front panel.
  1. Press and hold the round button until Curr, PWr, and EnEr are displayed in the three lines
  2. Select EnEr and press the round button
  3. Confirm the reset and enter the front panel password
  4. Press and hold the round button to exit
For revenue sealed meters, energy resets are not permitted.