How to connect 3-Wire Modbus to an ION Meter

The Shield and GND (ground) connections are internally connected in an ION meter using a diode bridge.


This is the best wiring solution for connecting a 3-Wire RS-485 device to an ION Meter (COM1 or COM2).

NOTE: The fourth wire (Shield) should still be present in the communication wire bundle, but left unconnected at the ION meter.




Last Revised: October 15, 2007
Public
All content © 1992-2007 Schneider Electric


Legacy KB System (APS) Data: RESL188498 V1.0, Originally authored by KBAdPM on 10/17/2007, Last Edited by KBAdPM on 10/17/2007
Related ranges: ION8800, ION8600, ION7550/ION7650, ION7300, ION6200, ION8500, ION8400, ION8300, ION7700, ION7500/ION7600