Advanced Reports error when creating Usage Reports: [ERR_16]Error publishing report (NAME) cannot be created under the given folder (number) because it must be under folder number 23 either directly or indirectly.

Below is a screen capture of the actual error:


  • Resolution

    The folder or folders that Advanced Reports is attempting to save to, does not exist.

    • 1. Go to the Admin tab and select Crystal Management Console.
      2. Log in using Administrator as username and leave the password section blank.
      3. Browse to Folders and follow the hierarchy below and create the folders and sub-folders as they appear with the same names and capitalization.
      4. Double check the PowerLogic Reports folder rights as well.


Legacy KB System (APS) Data: RESL187362 V3.0, Originally authored by PhHa on 08/02/2007, Last Edited by MaTh on 11/02/2012