Microsoft JScript runtime error: Automation Server cannot create object /powerlogicweb/Login.asp when trying to log into SMSWeb

After entering your login information and clicking Login, a Microsoft JScript runtime error is displayed:
Script error on line 30 (error 800a01ad)

On the System Manager Software server machine, re-register LoginControl.dll, PMO_DAL.dll, and PWLOGIN.dll.
These files are located in the following directory:

C:\POWERLOGIC\SMS\Web\ServerIISObjects

The following commands can be run from the Windows Run prompt

regsvr32 "C:\POWERLOGIC\SMS\Web\ServerIISObjects\LoginControl.dll"
regsvr32 "C:\POWERLOGIC\SMS\Web\ServerIISObjects\PMO_DAL.dll"
regsvr32 "C:\POWERLOGIC\SMS\Web\ServerIISObjects\PWLOGIN.dll"



Script error on lines 113 & 140

Delete the PSInstaller class from C:\Windows\Downloaded Program Files\ on the client machine. This will be re-downloaded the next time SMSWeb is accessed.

Legacy KB System (APS) Data: RESL186138 V2.0, Originally authored by KBAdPM on 07/04/2007, Last Edited by MaTh on 01/21/2011
Related ranges: System Manager 4.3, System Manager 4.2, System Manager 4.0, System Manager 3.3