What ethernet ports are used by System Manager Software (SMS)?

 

text
The user must be an Administrator or PowerUser on the server (for installation the user has to be an Administrator)

> Port 80 has to be open for HTTP access via IIS (access by remote browser)

> Port 8888 has to be open for PowerLogic Network Server (local server only)

> Port 8889 has to be open for Alarm Event Server access (local server only)

> Port 1433 has to be open for the SMS database (local server only)

> Port 1240 has to be open for the Browser Connection Manager (local PC only)

>Port 20978 has to be open for the Alarm Web Service

>Port 502 has to be open for Modbus TCP

>Port 21 has to be open for FTP

>Port 102 has to be open if using TCP/MMS (EGW drivers) 