ION7300 series communications loss when reading registers via Modbus TCP/IP

Issue
ION7300 series communications loss when reading registers via Modbus TCP/IP

Product Line
ION7300 Series Meters (ION7300, ION7330, and ION7350)

Cause 
The cause of the behavior is the Ethernet stack holding the ports open after a connection has been severed improperly. 
As the device believes there is still a connection, it will not accept any incoming requests, and it will hold this state continuously. 

Environment
The user will lose communications with the meter via Modbus TCP over Ethernet even though the user can still ping the meter.

Resolution
The only methods of resetting the socket connections are to either power cycle the device or change the meters IP address. 
This will clear the Ethernet stack and remove any current broken connections. 

In addition, review FA212335 for Ethernet ports and socket summary on ION Meters.