Technical FAQs

Ask a Question

Which EM4800 Current Transformers (CT's) require shorting blocks?

Issue
Which EM4800 Current Transformers (CT's) require shorting blocks?
 
Product Line
E4800 and EM4800
 
Cause
Customer would like to know which EM4800 CT's requires shorting block.
 
Environment
Install the shorting block with EM4800 CT's.
 
Resolution
When using 80 mA CTs or 5 A CT's, shorting blocks are recommended. 333 mV CT's do not require shorting blocks because they have a burden resistor built into the CT that limits the output voltage to 333 mV under all conditions. 

NOTE: If a 1/3 V CT was shorted, the internal burden resistor and the CT would be shorted at the same time. This would effectively be the same as shorting a current secondary CT and would cause no harm, despite the fact that it is not needed.
Was this helpful?
What can we do to improve the information ?