What type of RS485 cable is required for daisy-chaining Enercept meters?

What RS485 cable is required to wire Enercept meters.

Product Line
Enercept Meter

Communication Wiring

A twisted pair type of cable should be used in order to reduce radiated emissions and improve immunity of the communications system to any external electromagnetic interference. 
The Enercept meter has a 2-wire RS485 port. Belden 1120A, 9841 cable or equivalent cable is recommended to communicate or daisy chain with Enercept meters. 